| Terminal thickness: 5.2 | ||||
| Rigid conductor | Flexible conductor | I | Ui | |
| (mm2) | (A) | (V) | ||
| IEC 60947-7-1 | 0.2-4 | 0.2-2.5 | 24 | 500 |
Description | Color | Schematic diagram | Type | Part Number | Package quantity | |
Terminal: With general-purpose locating base, suitable for standard mounting rails and | Grey | JWD1-2.5/2 | 5 574 193 | 60 | ||
Blue | JWD1-2.5/2 BU | 5 574 194 | 60 | |||
Top and bottom interconnected terminals: The mounting and use methods are the same as above; the conducting plates in the upper and lower layers are interconnected to achieve the same potential of top and bottom connecting points. | Grey | |||||
Blue | ||||||
(1) End plate: (thickness: 2.5) One additional piece must be attached to the end of each terminal strip set. If it is mounted in the center of the terminal strip, the creepage distance may increase. | Grey | 2.5-4/2 G | 8 050 110 | 50 | ||
Blue | 2.5-4/2 G BU | 8 050 111 | 50 | |||
(2) Compensating end plate: (thickness: 2.5) It is used to offset interlayer displacement while it is adjacent to an ordinary terminal. | Grey | 2.5-4/2BD | 8 053 101 | 50 | ||
Blue | 2.54/2BD BU | 8 053 102 | 50 | |||
(3) Compensating end plate: (thickness: 2.5) It is used for terminal locating and fastening of the terminal strip or for offsetting interlayer displacement while it is arranged with other terminals in the same group. | 2.5-4/2 BD-1 | 8 053 105 | 50 | |||
(4) Central liaison part: It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will. | ZLB5/10 | 5 585 310 | 50 | |||
(5) Connecting sheet: For central connection of more than 10 digits | LJ 5/2 | 5 583 102 | 100 | |||
(6) Edge liaison part: Its role is the same as that of the central liaison part (4); with insulation on the back side; 10 digits that can be further divided at will | 2 digits: | BL5/2 | 5 582 112 | 200 | ||
3 digits: | BL5/3 | 5 582 113 | 200 | |||
10 digits: | BL5/10 | 5 582 120 | 100 | |||
(7) Jumping liaison part: With the spacer (8), it can connect any non-adjacent terminals in the center to form a jumping liaison terminal group. | KL5/10 | 5 584 120 | 50 | |||
(8) Spacer: Used as a spacer block between the accessory of the jumping liaison part (7) and the conductive part of the terminal | KB5 | 8 510 105 | 2000 | |||
(9) Divider: It is used to separate two adjacent liaison terminal groups and can be inserted after assembly, without any effect on the overall space. | GP-1 | 8 751 102 | 500 | |||
(10) Group partition: (thickness: 2.5) Used for separation of each terminal group; with dual effects (visible grouping and electrical isolation) | 2.5-4/2 GF | 8 750 108 | 50 | |||
(11) Tag: | ZP5 | 8 868 102 | 100 | |||
Terminal dimensions | ||||||
Thickness / width / end plate thickness | [mm] | 5.2/56/2.5 | ||||
Height (TH 35:7.5 / TH 35:15 / G 32:15) | [mm] | 62/69.5/67 | ||||
Technical data based on IEC/DIN VDE standards | ||||||
Maximum rated working current / cross-sectional area | [A] / [mm2] | 32/4 | ||||
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is used: | [mm2] | 2.5/2.5 | ||||
Rated impulse withstand voltage / degree of pollution | [kV]/- | 6/3 | ||||
Over-voltage category / insulation material group | -/- | lll/l | ||||
Connection capacity | ||||||
Flexible conductor with tubular bare terminal / tubular pre-insulated terminal | [mm2] | 0.25-2.5 / 0.25-1.5 | ||||
Connection of multiple conductors (two conductors with the same cross-sectional area) | ||||||
Rigid conductor / flexible conductor | [mm2] | 0.2-1/0.2-1.5 | ||||
Flexible conductor with tubular bare terminal | [mm2] | 0.25-1.5 | ||||
Flexible conductor with DEV-tubular pre-insulated terminal | [mm2] | 0.5-1 | ||||
Stripping length | [mm] | 8 | ||||
Screw type | M3 | |||||
Torque | [Nm] | 0.6-0.8 | ||||
Insulation material type | PA | |||||
Material flammability according to UL94 | V0 | |||||
Rated working voltage / rated working current / wire gauge | UL:[V]/[A]/AWG | 600/20/28-12 | ||||
Note: When an edge liaison part is used, a cable below 1.5 mm2 should be used for a 2.5 mm2 terminal; corresponding cables should be used for terminals with other cross-sectional areas (mm2). | ||||||
English